Thermal Inspection of a 30.54 MW Ground-Mounted Solar Plant

Drone-based RGB and thermal inspection of the solar plant in Borgdorf-Seedorf, Germany, covering 47,448 photovoltaic modules to identify and assess suspected thermal anomalies requiring maintenance attention.

Utility-scale30.54 MWpThermal + RGBIEC 62446-3 Compliant Thermographic InspectionBorgdorf-Seedorf, Germany2026-08

Hakan Yaralı · Technical Manager

Aerial view of solar panel rows separated by green vegetation

Project at a Glance

Plant capacity
30.54 MWp
Modules inspected
47,448
Inspection area
~20.830 ha
Data captured
Thermal + RGB
Inspection duration
1 day
Suspected anomalies
9,551
Location
Borgdorf-Seedorf, Germany
Inspection date
2026-08
Inspection standard
IEC 62446-3 Compliant Thermographic Inspection

Project Context

The solar plant in Borgdorf-Seedorf, Germany operates where vegetation growth has become an increasingly important factor in plant performance and site management. Over time, unmanaged vegetation around and between the module rows has contributed to more frequent shading, while also increasing the potential fire risk across parts of the site. The plant has an installed capacity of 30.54 MWp DC.

Inspection Scope

What was inspected

  • Thermal and RGB imagery of all covered module rows
  • 12,288 LONGi LR7-72HYD-640M bifacial modules
  • 35,160 LONGi LR7-72HYD-645M bifacial modules
  • A total of 47,448 photovoltaic modules were included in the inspection scope
  • AI-assisted anomaly screening at module level
  • Detection and classification of module and string-level thermal anomalies
  • Technical review of identified findings
  • Prioritization based on estimated operational impact

Methodology

  1. 1

    Pre-flight planning

    Flight altitude was defined to achieve a 3 cm/pixel GSD in accordance with IEC 62446-3 requirements, while overlap and flight route were planned according to the plant layout.

  2. 2

    RGB and thermal data acquisition

    Thermal and RGB imagery was captured across the inspected photovoltaic array.

  3. 3

    Image quality control and alignment

    Coverage and thermal image integrity were checked and imagery was georeferenced for analysis.

  4. 4

    AI-assisted anomaly screening

    Thermal patterns were detected, grouped and mapped to individual photovoltaic modules.

  5. 5

    Technical review

    Detected findings were reviewed and classified according to their thermal characteristics.

  6. 6

    Reporting and verification plan

    Prioritized findings were delivered to the client together with efficiency and loss-impact assessments to support subsequent maintenance activities.

Findings

FindingDetected patternPossible causeVerificationStatus
Open Circuit StringElectrical continuity is interrupted, causing the entire string to become inactive.Blown fuse, damaged or disconnected cable, faulty connector, or another interruption within the string circuit.Thermal measurement and visual inspection: reported; further field verification may be required.Pending
HotspotA localized area reaches an abnormally high temperature compared with its surroundings.Cell damage, microcracks, physical defects, shading, contamination, or other conditions that cause abnormal localized heating.Thermal measurement and visual inspection: reported; further field verification may be required.Pending
Cell FaultA PV cell loses normal function, causing localized heating and reduced performance.Manufacturing defects, microcracks, physical damage, or deterioration of the affected cell.Thermal measurement and visual inspection: reported; further field verification may be required.Pending

Thermal Evidence

Thermal image

Grayscale thermal view of solar panel rows with bright areas near vegetation

RGB image

Aerial view of solar panel rows separated by green vegetation
Thermal and RGB views of module rows at Borgdorf-Seedorf. Vegetation is visible along module edges; thermal patterns indicate areas requiring further investigation.

Actions and Outcome

  • Vegetation was found to be concentrated along the lower edges of several PV strings and around module edges, creating localized shading and additional thermal stress in the most affected areas.
  • Modules exposed to heavier vegetation showed a higher occurrence of cell and multicell anomalies, particularly along the affected edges, indicating areas where vegetation management and module-level maintenance should be prioritized.
  • The additional efficiency loss and estimated financial impact associated with these affected modules were assessed to help the O&M team identify where corrective action could provide the greatest operational benefit.
  • An unusually high number of open circuit string anomalies was detected across the plant. Further assessment of their distribution indicated that 20 inverters were non-operational during the inspection.
  • All findings were prioritized according to their estimated impact on plant efficiency, energy production, and financial loss, providing the client with a clear basis for maintenance planning and field intervention.

Limitations

Thermal imagery can identify temperature patterns requiring investigation, but it does not independently confirm every electrical or mechanical root cause. Irradiance, wind, reflections, shading, soiling, flight conditions and equipment configuration may affect interpretation.

Other case studies

Aerial view of rooftop solar panels with shadows from a raised structure

Thermal Inspection of a 745 kW Photovoltaic Plant

Drone-based thermal and RGB inspection of the photovoltaic plant in Kaštel Sućurac, Croatia, covering 1,755 modules to identify thermal anomalies associated with external shading and support performance assessment and maintenance prioritization.

745 kWpThermal + RGBIEC 62446-3 Compliant Thermographic Inspection
Aerial view of rooftop solar panels with extensive white surface deposits

Thermal Inspection of a 462 kW Rooftop Solar Plant

Drone-based thermal and RGB inspection of a rooftop photovoltaic plant in Kaštel Sućurac, Croatia, covering 1,089 half-cut modules to identify thermal anomalies and support performance assessment and maintenance prioritization.

462 kWpThermal + RGBIEC 62446-3 Compliant Thermographic Inspection

Planning a photovoltaic inspection?

Share your plant capacity, module count and inspection objective to receive a proposed inspection scope.

Request an Inspection Scope