Thermal Inspection of a 199.875 kW Rooftop Solar Plant
Drone-based thermal and RGB inspection of a rooftop photovoltaic plant in Italy, covering 975 modules to identify thermal anomalies, visible module damage, and conditions affecting plant performance and maintenance priorities.
Hakan Yaralı · Accredited Technical Manager

Project at a Glance
- Plant capacity
- 199.875 kW
- Modules inspected
- 975
- Inspection area
- ~0.286 ha
- Data captured
- Thermal + RGB
- Inspection duration
- 1 field day
- Suspected anomalies
- 342
- Location
- Italy
- Inspection date
- 2026-08
- Inspection standard
- IEC 62446-3 Compliant Thermographic Inspection
Project Context
Visible burn marks and surface damage were identified on several PV modules during the inspection. These affected areas were associated with abnormal thermal behavior, particularly cell and hotspot anomalies, indicating localized heating and reduced module performance. Drone-based thermal and RGB inspection allowed the visible damage to be evaluated together with its thermal impact, helping the maintenance team identify the most affected modules and prioritize corrective action.
Inspection Scope
What was inspected
- Thermal and RGB imagery across the rooftop photovoltaic array
- 975 photovoltaic modules included in the inspection scope
- Assessment of visible burn marks and surface damage affecting module condition
- Assessment of contamination and other visible conditions affecting module performance
- AI-assisted anomaly screening at module level
- Detection and classification of open circuit string, cell, hotspot, multicell, multi-hotspot, diode, junction box, open circuit module, and short circuit module anomalies
- Cross-assessment of thermal findings with RGB observations
- Technical review of identified anomalies
- Prioritization based on estimated operational, efficiency, and financial impact
Methodology
- 1
Pre-flight planning
Flight altitude was defined to achieve a 3 cm/pixel GSD in accordance with IEC 62446-3 requirements, while overlap and flight route were planned according to the plant layout.
- 2
RGB and thermal data acquisition
Thermal and RGB imagery was captured across the inspected photovoltaic array.
- 3
Image quality control and alignment
Coverage and thermal image integrity were checked and imagery was georeferenced for analysis.
- 4
AI-assisted anomaly screening
Thermal patterns were detected, grouped and mapped to individual photovoltaic modules.
- 5
Technical review
Detected findings were reviewed and classified according to their thermal characteristics.
- 6
Reporting and verification plan
Prioritized findings were delivered to the client together with efficiency and loss-impact assessments to support subsequent maintenance activities.
Findings
| Finding | Detected pattern | Possible cause | Verification | Status |
|---|---|---|---|---|
| Open Circuit String | Electrical continuity is interrupted, causing the entire string to become inactive. | Blown fuse, damaged or disconnected cable, faulty connector, or another interruption within the string circuit. | Thermal measurement and visual inspection | Reported |
| Cell Fault | A PV cell loses normal function, causing localized heating and reduced performance. | Manufacturing defects, microcracks, physical damage, or deterioration of the affected cell. | Thermal measurement and visual inspection | Reported |
| Hotspot | A localized area reaches an abnormally high temperature compared with its surroundings. | Cell damage, microcracks, physical defects, shading, contamination, or other conditions that cause abnormal localized heating. | Thermal measurement and visual inspection | Reported |
| Multicell Fault | Multiple PV cells within the same module lose normal function, causing wider performance and power loss. | Manufacturing defects, thermal stress, or physical damage affecting multiple cells within the module. | Thermal measurement and visual inspection | Reported |
| Multi Hotspot | Multiple localized areas within the same module reach abnormally high temperatures. | Multiple cell defects, microcracks, physical damage, contamination, or localized electrical resistance. | Thermal measurement and visual inspection | Reported |
| Diode Fault | Uniform heating across a module substring indicates that the affected cell group is being bypassed. | Bypass diode short circuit or continuous conduction, causing current to bypass the affected substring. | Thermal measurement and visual inspection | Reported |
| Junction Box | Localized heating is concentrated around the module junction box area. | Loose or resistive connections, internal junction box damage, or component-related electrical stress. | Thermal measurement and visual inspection | Reported |
| Open Circuit Module | Current flow through the module is interrupted, preventing the module from operating normally. | Internal connection failure, damaged conductors, connector faults, or interruption within the module circuit. | Thermal measurement and visual inspection | Reported |
| Short Circuit Module | Abnormal heating across the module indicates unintended current flow within the internal circuit. | An unintended conductive path between positive and negative poles, causing short-circuit behavior within the string. | Thermal measurement and visual inspection | Reported |
Thermal Evidence
Thermal image

RGB image

Actions and Outcome
- A total of 342 faulty panels were identified and reported to the client.
- Visible burn marks and surface damage were observed on affected modules and were associated with a high occurrence of cell and hotspot anomalies.
- Thermal analysis identified 136 open circuit string, 104 cell fault, and 95 hotspot findings, showing that the most affected areas were concentrated around modules with visible damage and contamination-related conditions.
- Modules showing both visible damage and abnormal thermal behavior were prioritized for maintenance review.
- Findings were prioritized according to their estimated impact on plant efficiency, energy production, and financial loss.
Limitations
Thermal imagery can identify temperature patterns requiring investigation, but it does not independently confirm every electrical or mechanical root cause. Irradiance, wind, reflections, shading, soiling, flight conditions and equipment configuration may affect interpretation.
Other case studies

Thermal Inspection of a 3.60 MW Rooftop Solar Plant
Drone-based thermal and RGB inspection of a rooftop photovoltaic plant in Türkiye, covering 12,703 modules to identify thermal anomalies, physical module issues, and conditions affecting plant performance and maintenance priorities.

Thermal Inspection of an 827.48 kW Solar Plant
Drone-based thermal and RGB inspection of a photovoltaic plant in Italy, covering 1,948 modules to identify thermal anomalies associated with visible module damage and support performance assessment and maintenance prioritization.

Planning a photovoltaic inspection?
Share your plant capacity, module count and inspection objective to receive a proposed inspection scope.
Request an Inspection Scope