Thermal Inspection of a 3.60 MW Rooftop Solar Plant

Drone-based thermal and RGB inspection of a rooftop photovoltaic plant in Türkiye, covering 12,703 modules to identify thermal anomalies, physical module issues, and conditions affecting plant performance and maintenance priorities.

Rooftop3,601.4 kWThermal + RGBIEC 62446-⁠3 Compliant Thermographic InspectionTürkiye2026-11

Hakan Yaralı · Accredited Technical Manager

Aerial view of rooftop solar rows on a metal roof with one displaced module resting on the array

Project at a Glance

Plant capacity
3,601.4 kW
Modules inspected
12,703
Inspection area
~5.81 ha
Data captured
Thermal + RGB
Inspection duration
1 field day
Suspected anomalies
1,580
Location
Türkiye
Inspection date
2026-11
Inspection standard
IEC 62446-⁠3 Compliant Thermographic Inspection

Project Context

A displaced PV module was identified during the inspection after becoming detached from its original position and falling onto adjacent modules. The displaced module physically covered part of the surrounding array, creating localized shading and preventing the affected modules underneath from operating normally. Drone-based thermal and RGB inspection allowed this physical condition to be evaluated together with its thermal impact, helping the maintenance team identify the affected modules and prioritize corrective action.

Inspection Scope

What was inspected

  • Thermal and RGB imagery across the rooftop photovoltaic array
  • 12,703 photovoltaic modules included in the inspection scope
  • Assessment of the displaced module and its impact on adjacent PV modules
  • Assessment of shading, contamination, and other visible conditions affecting module performance
  • AI-assisted anomaly screening at module level
  • Detection and classification of hotspot, cell, multi-hotspot, junction box, multicell, open circuit string, diode, open circuit module, and multi-diode anomalies
  • Cross-assessment of thermal findings with RGB observations
  • Technical review of identified anomalies
  • Prioritization based on estimated operational, efficiency, and financial impact

Methodology

  1. 1

    Pre-flight planning

    Flight altitude was defined to achieve a 3 cm/pixel GSD in accordance with IEC 62446-⁠3 requirements, while overlap and flight route were planned according to the plant layout.

  2. 2

    RGB and thermal data acquisition

    Thermal and RGB imagery was captured across the inspected photovoltaic array.

  3. 3

    Image quality control and alignment

    Coverage and thermal image integrity were checked and imagery was georeferenced for analysis.

  4. 4

    AI-assisted anomaly screening

    Thermal patterns were detected, grouped and mapped to individual photovoltaic modules.

  5. 5

    Technical review

    Detected findings were reviewed and classified according to their thermal characteristics.

  6. 6

    Reporting and verification plan

    Prioritized findings were delivered to the client together with efficiency and loss-impact assessments to support subsequent maintenance activities.

Findings

FindingDetected patternPossible causeVerificationStatus
HotspotA localized area reaches an abnormally high temperature compared with its surroundings.Cell damage, microcracks, physical defects, shading, contamination, or other conditions that cause abnormal localized heating.Thermal measurement and visual inspectionReported
Cell FaultA PV cell loses normal function, causing localized heating and reduced performance.Manufacturing defects, microcracks, physical damage, or deterioration of the affected cell.Thermal measurement and visual inspectionReported
Multi HotspotMultiple localized areas within the same module reach abnormally high temperatures.Multiple cell defects, microcracks, physical damage, contamination, or localized electrical resistance.Thermal measurement and visual inspectionReported
Junction BoxLocalized heating is concentrated around the module junction box area.Loose or resistive connections, internal junction box damage, or component-related electrical stress.Thermal measurement and visual inspectionReported
Multicell FaultMultiple PV cells within the same module lose normal function, causing wider performance and power loss.Manufacturing defects, thermal stress, or physical damage affecting multiple cells within the module.Thermal measurement and visual inspectionReported
Open Circuit StringElectrical continuity is interrupted, causing the entire string to become inactive.Blown fuse, damaged or disconnected cable, faulty connector, or another interruption within the string circuit.Thermal measurement and visual inspectionReported
Diode FaultUniform heating across a module substring indicates that the affected cell group is being bypassed.Bypass diode short circuit or continuous conduction, causing current to bypass the affected substring.Thermal measurement and visual inspectionReported
Open Circuit ModuleCurrent flow through the module is interrupted, preventing the module from operating normally.Internal connection failure, damaged conductors, connector faults, or interruption within the module circuit.Thermal measurement and visual inspectionReported
Multi DiodeMultiple substrings within the same module show abnormal and uniform thermal behavior.Multiple bypass diodes remaining in conduction or developing electrical faults within the module.Thermal measurement and visual inspectionReported

Thermal Evidence

Thermal image

Thermal grayscale image of a rooftop solar array with a displaced module lying across adjacent panels

RGB image

Aerial view of rooftop solar rows on a metal roof with one displaced module resting on the array
Thermal and RGB views of the 3.60 MW rooftop plant in Türkiye, showing a displaced module resting on adjacent modules. Visible RGB findings that coincide with thermal anomalies provide useful diagnostic context but should not automatically be considered the confirmed cause. Additional field verification may be required to establish the underlying root cause.

Actions and Outcome

  • A total of 1,580 faulty panels were identified and reported to the client.
  • A displaced PV module was identified resting on adjacent modules, physically obstructing the affected area and preventing the covered modules from operating normally.
  • Thermal analysis showed a high occurrence of hotspot and cell anomalies, with 565 hotspot findings and 563 cell faults identified across the inspected plant.
  • The area affected by the displaced module was prioritized for corrective action to restore normal operation and prevent further performance loss or physical damage.
  • Findings were prioritized according to their estimated impact on plant efficiency, energy production, and financial loss.

Limitations

Thermal imagery can identify temperature patterns requiring investigation, but it does not independently confirm every electrical or mechanical root cause. Irradiance, wind, reflections, shading, soiling, flight conditions and equipment configuration may affect interpretation.

Other case studies

Aerial view of a rooftop solar array with visible cracking on many photovoltaic modules

Thermal Inspection of an 827.48 kW Solar Plant

Drone-based thermal and RGB inspection of a photovoltaic plant in Italy, covering 1,948 modules to identify thermal anomalies associated with visible module damage and support performance assessment and maintenance prioritization.

827.48 kWThermal + RGBIEC 62446-⁠3 Compliant Thermographic Inspection
Aerial view of rooftop solar panels with shadows from a raised structure

Thermal Inspection of a 745 kW Photovoltaic Plant

Drone-based thermal and RGB inspection of the photovoltaic plant in Kaštel Sućurac, Croatia, covering 1,755 modules to identify thermal anomalies associated with external shading and support performance assessment and maintenance prioritization.

745 kWpThermal + RGBIEC 62446-⁠3 Compliant Thermographic Inspection

Planning a photovoltaic inspection?

Share your plant capacity, module count and inspection objective to receive a proposed inspection scope.

Request an Inspection Scope