Thermal Inspection of an 827.48 kW Solar Plant
Drone-based thermal and RGB inspection of a photovoltaic plant in Italy, covering 1,948 modules to identify thermal anomalies associated with visible module damage and support performance assessment and maintenance prioritization.
Hakan Yaralı · Accredited Technical Manager

Project at a Glance
- Plant capacity
- 827.48 kW
- Modules inspected
- 1,948
- Inspection area
- ~1.71 ha
- Data captured
- Thermal + RGB
- Inspection duration
- 1 field day
- Suspected anomalies
- 365
- Location
- Italy
- Inspection date
- 2026-11
- Inspection standard
- IEC 62446-3 Compliant Thermographic Inspection
Project Context
A high level of visible cracking was identified across the PV modules, making physical module damage one of the main conditions affecting the site. These damaged modules showed a higher occurrence of multi-hotspot, cell, and multicell thermal anomalies, indicating localized heating and reduced module performance. Drone-based thermal and RGB inspection allowed the damaged modules to be evaluated together with their thermal behavior, helping the maintenance team identify the most affected areas and prioritize corrective actions.
Inspection Scope
What was inspected
- Thermal and RGB imagery across the photovoltaic array
- 1,948 photovoltaic modules included in the inspection scope
- Assessment of visible cracks and physical module damage
- Assessment of contamination and shading conditions across affected modules
- AI-assisted anomaly screening at module level
- Detection and classification of multi-hotspot, hotspot, open circuit string, cell, multicell, open circuit module, and diode anomalies
- Cross-assessment of thermal findings with RGB observations
- Technical review of identified anomalies
- Prioritization based on estimated operational and performance impact
Methodology
- 1
Pre-flight planning
Flight altitude was defined to achieve a 3 cm/pixel GSD in accordance with IEC 62446-3 requirements, while overlap and flight route were planned according to the plant layout.
- 2
RGB and thermal data acquisition
Thermal and RGB imagery was captured across the inspected photovoltaic array.
- 3
Image quality control and alignment
Coverage and thermal image integrity were checked and imagery was georeferenced for analysis.
- 4
AI-assisted anomaly screening
Thermal patterns were detected, grouped and mapped to individual photovoltaic modules.
- 5
Technical review
Detected findings were reviewed and classified according to their thermal characteristics.
- 6
Reporting and verification plan
Prioritized findings were delivered to the client together with efficiency and loss-impact assessments to support subsequent maintenance activities.
Findings
| Finding | Detected pattern | Possible cause | Verification | Status |
|---|---|---|---|---|
| Multi Hotspot | Multiple localized areas within the same module reach abnormally high temperatures. | Multiple cell defects, microcracks, physical damage, contamination, or localized electrical resistance. | Thermal measurement and visual inspection | Reported |
| Hotspot | A localized area reaches an abnormally high temperature compared with its surroundings. | Cell damage, microcracks, physical defects, shading, contamination, or other conditions that cause abnormal localized heating. | Thermal measurement and visual inspection | Reported |
| Open Circuit String | Electrical continuity is interrupted, causing the entire string to become inactive. | Blown fuse, damaged or disconnected cable, faulty connector, or another interruption within the string circuit. | Thermal measurement and visual inspection | Reported |
| Cell Fault | A PV cell loses normal function, causing localized heating and reduced performance. | Manufacturing defects, microcracks, physical damage, or deterioration of the affected cell. | Thermal measurement and visual inspection | Reported |
| Multicell Fault | Multiple PV cells within the same module lose normal function, causing wider performance and power loss. | Manufacturing defects, thermal stress, or physical damage affecting multiple cells within the module. | Thermal measurement and visual inspection | Reported |
| Open Circuit Module | Current flow through the module is interrupted, preventing the module from operating normally. | Internal connection failure, damaged conductors, connector faults, or interruption within the module circuit. | Thermal measurement and visual inspection | Reported |
| Diode Fault | Uniform heating across a module substring indicates that the affected cell group is being bypassed. | Bypass diode short circuit or continuous conduction, causing current to bypass the affected substring. | Thermal measurement and visual inspection | Reported |
Thermal Evidence
Thermal image

RGB image

Actions and Outcome
- A total of 365 affected modules were identified and reported to the client.
- RGB analysis identified visible crack findings on 160 panels, making physical module damage one of the most prominent conditions observed across the site.
- A strong overlap was identified between visible cracking and thermal anomalies. Crack findings coincided with 131 multi-hotspot, 50 cell, 45 multicell, and 17 hotspot findings.
- The high concentration of multi-hotspot, cell, and multicell anomalies on visibly damaged modules highlighted areas where physical module damage was associated with increased localized heating and performance degradation.
- Modules showing both visible cracking and abnormal thermal behavior were prioritized for maintenance review due to their potential additional impact on efficiency, energy production, and financial loss.
- Estimated efficiency loss, annual energy-loss impact, and financial impact were calculated to support corrective-action and maintenance prioritization.
Limitations
Thermal imagery can identify temperature patterns requiring investigation, but it does not independently confirm every electrical or mechanical root cause. Irradiance, wind, reflections, shading, soiling, flight conditions and equipment configuration may affect interpretation.
Other case studies

Thermal Inspection of a 745 kW Photovoltaic Plant
Drone-based thermal and RGB inspection of the photovoltaic plant in Kaštel Sućurac, Croatia, covering 1,755 modules to identify thermal anomalies associated with external shading and support performance assessment and maintenance prioritization.

Thermal Inspection of a 462 kW Rooftop Solar Plant
Drone-based thermal and RGB inspection of a rooftop photovoltaic plant in Kaštel Sućurac, Croatia, covering 1,089 half-cut modules to identify thermal anomalies and support performance assessment and maintenance prioritization.